Product Introduction ¡¡¡¡This
series of fan coils are independently developed by our company on the basis of
combining superior features of other advanced products and designed and manufactured
according to national standards. They are mainly designed for central air conditioning
system and can be used to subsitute the traditional radiators that used in stores,
hospitals, office buildings, and airports. ¡¡¡¡ Besides, ultra-thin models are
alsow available for options. The series consists of 10 fundamental models: FP-3.5
(2.5), FP-5, FP-6.3, FP-7.1, FP-8, FP-10, FP-12.5, FP-14, FP-16, FP-20, with a
ventilation capacity ranging from 350 to 2000m3/h and refrigerating capacity ranging
from 2150W to 9750W. They can be classified, based on their forms, into ceiling
built-in type, floor mount built-in type, ceiling hanging type, floor mount type.
However, standard models and high static pressure models are also available. |
| | |
Ceiling Built-in Type | Ceiling Hanging
Type | Floor Mount
Type |
| Product Features ¡¡1.
Outstanding quality and stable performance ¡¡¡¡ The surface coolers of fan
coils are made of high quality copper tubes, aluminum foil and high strength galvanized
steel sheets that are closely linked through tube deflation to achieve best heat
transfer efficiency. ¡¡2. Stable running and low noise ¡¡¡¡
Thanks to the utilization of 3-speed motors and centrifugal wind wheels, the noise
level is greatly reduced and the wind output capacity is increased. Thermal insulation
and vibration reduction materials are used in every connection spot to create
you a quite and comfortable space. ¡¡3. Advanced technique, safe and reliable in
use ¡¡¡¡The company has a complete line of high automation equipment to produce
fan coils of high quality and each coil produced is strictly tested to meet the
requirement of high strength and impact resistance. Thus, the use safety can be
relied. ¡¡4. 3-level speed regulation ¡¡¡¡The speed
level can be adjusted at user's will to satisfy the needs for different wind volume.
¡¡5. Diversified types, easy to install ¡¡¡¡
The units are light and handy, only 23 cm thick. Ultra-thin type is only 20 cm
thick. The water inlet and outlet tubes and the electric lines are easy to connect
and the water flow directions and wind directions can be altered according to
the site needs.¡¡Various installation types available to meet your decoration needs. ¡¡6. Complete selection of types ¡¡¡¡The
coil range comes available in 10 types ranging from FP3.5 to FP20 for different
air conditioned areas. Besides, ultra-thin coil is available for extremely small
living space. | Illustration of Index Number
|
Featured
Difference: S stands for "Standard Type"(default), G stands for "High Static Pressure" |
Water Inlet: Z stands inlet
on the left, Y stands for inlet on the right | Air
Output: S stands for output from upper, Q stands for output from front |
Air Return: X stands for return
from bottom, H stands for return from back | Installation:
M stands for surface installation, A stands for secret installation |
Structure: L stands for vertical
type, W stands for horizontal type | Nominal
Air Volume: specified value X 100m3/h | Name
of Product: fan coil | | ¡¡Taking FP-6.3WAH-(Q)Y for example, it indicates
the product is a fan coil with a nominal air volume of 630m3/h, horizontal/secret
installed, back air returned and front output, standard type. |
Remarks: 1.
The water inlet direction shall be on the opposite of air output direction. |
2. If air return
is unmarked, it means there is no air return box. | | |
Technical Specifications
of Blower Engine Coil | |
| FP-3.5 | FP-5 | FP-6.3 | FP-7.1 | FP-8 |
air speed | high | mid | low | high | mid | low | high | mid | low | high | mid | low | high | mid | low |
output m3/h | 350 | 280 | 210 | 500 | 400 | 300 | 630 | 505 | 380 | 710 | 570 | 430 | 800 | 640 | 480 |
cooling capacity |
kcal/h | 1850 | 1610 | 1350 | 2600 | 2260 | 1900 | 3250 | 2830 | 2375 | 3690 | 2960 | 2690 | 4150 | 3610 | 3030 |
W | 2158 | 1878 | 1575 | 3033 | 2637 | 2217 | 3792 | 3300 | 2770 | 4305 | 3453 | 3140 | 4842 | 4212 | 3535 |
heating capacity |
kcal/h | 3145 | 2550 | 2020 | 4415 | 3580 | 2845 | 5520 | 4485 | 3555 | 6220 | 5060 | 4020 | 7050 | 5720 | 4535 |
W | 3669 | 2975 | 2357 | 5151 | 4177 | 3319 | 6440 | 5233 | 4148 | 7257 | 5903 | 4690 | 8225 | 6673 | 5291 |
maximum noise level
dB(A) | 36 | 28 | 24 | 38 | 30 | 26 | 39 | 34 | 31 | 41 | 38 | 32 | 43 | 38 | 32 |
water flow (kg/h) | 370 | 520 | 650 | 720 | 830 |
water resistance (KPa) | 0.38 | 0.75 | 1.34 | 1.75 | 2.12 |
maximum power (w) | 45 | 58 | 70 | 78 | 85 | |
|
| FP-10 | FP-12.5 | FP-14 | FP-16 | FP-20 |
air speed | high | mid | low | high | mid | low | high | mid | low | high | mid | low | high | mid | low |
output m3/h | 1000 | 800 | 600 | 1250 | 1000 | 750 | 1400 | 1120 | 840 | 1600 | 1280 | 960 | 2000 | 1600 | 1200 |
cooling capacity |
kcal/h | 4900 | 4265 | 3575 | 6000 | 5200 | 4380 | 6270 | 5820 | 4905 | 7750 | 6745 | 5660 | 9750 | 8485 | 7120 |
W | 5717 | 4976 | 4171 | 7000 | 6067 | 5110 | 7315 | 6790 | 5723 | 9042 | 7869 | 6603 | 11375 | 9899 | 8307 |
heating capacity |
kcal/h | 9680 | 7855 | 6220 | 11855 | 9615 | 7620 | 13278 | 10770 | 8535 | 15310 | 12425 | 9855 | 19260 | 15630 | 12310 |
W | 11293 | 9164 | 7257 | 13831 | 11218 | 8890 | 15491 | 12565 | 9958 | 17862 | 14496 | 11498 | 22470 | 18235 | 14362 |
maximum noise level
dB(A) | 44 | 39 | 33 | 45 | 33 | 23 | 46 | 33 | 26 | 48 | 37 | 25 | 52 | 44 | 31 |
water flow (kg/h) | 980 | 1200 | 1330 | 1550 | 1950 |
water resistance (KPa) | 3.29 | 0.98 | 1.06 | 1.56 | 2.7 |
maximum power (w) | 83 | 132 | 138 | 145 | 190 | |
| Remarks: ¡¡1. 3-speed
control for all models above; ¡¡2. capacity under air cooling condition: dry-bulb
temp. 27¡æ, wet-bulb temp. 19.5¡æ, water enter temp. 7¡æ, feed water temp. 12¡æ; ¡¡3.
capacity under air heating condition: dry-bulb temp. 21¡æ, water enter temp. 60¡æ; ¡¡4.
environment noise below 20dB(A), testing spot 1m far from the unit; ¡¡5. coil
pipes stand for the pressure test up to 3.0MPa, maximum working pressure allowed
1.68MPa; ¡¡6. 3-speed engine, input power source 200¡À10V(DC), 50¡À2.5Hz; ¡¡7.
water input pipe:ZG3/4 female screw, water condensing pipe: ZG3/4 male screw |
| Instruction to Use: |
| Please note that all
fan coils shall be installed, utilized and maintained by or under the instructions
of professionals so as to avoid hurts or damages to operators and equipment.
1. Check before the
installation whether the unit is kept in good condition and with complete components,
whether the joints are fastened firmly. Wind wheel shall be strictly protected
from striking or impact during the transportation. 2. The unit shall
be installed accurately in horizontal direction so as the condensed water can
be drained smoothly. 3. Please use soft
pipes to connect unit and water supply system, and the copper joint shall be fastened
solidly with spanner to protect the unit from possible damages. 4. All water pipes
shall be wrapped with thermal insulation materials. 5. The power source
used is single phase, 220¡À10V and 50¡À5HZ. Be noted that the phase wire shall be
introduced into the motor from the beginning end and all joints shall be connected
in maximum security to avoid potential dangers. Units in different types shall
not share a same control switch. 6. The vent valve
mounted above the joint of return pipes shall be opened before running and closed
after the water tank is imbued. 7. The working temperature
of unit is 600¡æ¡«650¡æ and the flow speed
is 0.5¡«2.0m/s(suggested to select within the range of
0.5¡«1.0m/s) 8. The heat exchanger
shall be cleaned from time to time to maintain a good heat transfer performance,
and the filter net shall be cleaned regularly to keep a smooth air return. | | | | | |
| |